stc1000p

STC-1000+ One vessel brew system controller

This is a firmware and Arduino based uploader for the STC-1000 dual stage thermostat. The purpose is to serve as a simple semi-automatic controller for a one vessel brewing system.

STC-1000

Features

Parameters

Menu item Description Values
Sd Strike delay 0-999 minutes
St Strike water setpoint -40.0 to 140°C or -40.0 to 250°F
SO Strike output (also used to reach hotbreak and between mash steps) 0-200%
Pt1 Mash step 1 setpoint -40.0 to 140°C or -40.0 to 250°F
Pd1 Mash step 1 duration 0-999 minutes
Pt2 Mash step 2 setpoint -40.0 to 140°C or -40.0 to 250°F
Pd2 Mash step 2 duration 0-999 minutes
Pt3 Mash step 3 setpoint -40.0 to 140°C or -40.0 to 250°F
Pd3 Mash step 3 duration 0-999 minutes
Pt4 Mash step 4 setpoint -40.0 to 140°C or -40.0 to 250°F
Pd4 Mash step 4 duration 0-999 minutes
Pt5 Mash step 4 setpoint -40.0 to 140°C or -40.0 to 250°F
Pd5 Mash step 4 duration 0-999 minutes
Pt6 Mash step 4 setpoint -40.0 to 140°C or -40.0 to 250°F
Pd6 Mash step 4 duration 0-999 minutes
PO Mashing output -200 to 200%
Ht Hot break temperature -40.0 to 140°C or -40.0 to 250°F
HO Hot break output -200 to 200%
Hd Hot break duration 0-999 minutes
bO Boil output -200 to 200%
bd Boil duration 0-999 minutes
hd1 Hop alarm 1 0-999 minutes
hd2 Hop alarm 2 0-999 minutes
hd3 Hop alarm 3 0-999 minutes
hd4 Hop alarm 4 0-999 minutes
tc Temperature correction -5.0 to 5°C or -10.0 to 10.0°F
APF Alarm/Pause control flags 0 to 511
PF Pump control flags 0 to 31
Pd Set heating period interval 1.0 to 20.0 seconds
cO Manual mode output -200 to 200%
cP Manual mode pump 0 (=off) or 1 (=on)
cSP Manual mode thermostat setpoint -40.0 to 140°C or -40.0 to 250°F
ASd Safety shutdown timer 0-999 minutes
rUn Run mode OFF, Pr (run program), Ct (manual mode thermostat), Co (manual mode constant output)

Note on APF parameter: APF is a parameter that holds flags to enable/disable the alarm/pause points during the program. By default all alarms/pause points are enabled, but this parameter allows the user to skip some/all of them if so desired. To make adjustments, the desired behaviour needs to be calculated.

Value Description
1 Strike temp reached/dough in alarm
2 Strike temp reached/dough in pause
4 Mash done/sparge/start boil up alarm
8 Mash done/sparge/start boil up pause
16 Hop addition 1 alarm
32 Hop addition 2 alarm
64 Hop addition 3 alarm
128 Hop addition 4 alarm
256 Boil done/start chill alarm

Add up the values for the alarms/pause points desired, and set that value to the APF parameter. Say for example you’d like to mash in cold, and want the controller to skip the alarm and pause after strike temp is reached, and just continue with the mash profile (but still keep the other alarms/pause points). Then sum up all the alarms (511) and subtract 1 (strike temp reached alarm) and 2 (strike temp reached pause). The value (508) is what you’d want to enter in APF.

Note on PF parameter: The PF parameter holds flags to indicate pump status during different stages of the program. By default the pump is on during the mash.

Value Description
1 Pump during heating of strike water
2 Pump during ramping up to reach next mash steps
4 Pump during the mash steps
8 Pump during heating up to reach hot break
16 Pump during hot break

Similar to the APF parameter. Add upp the values of the stages when the pump should be active and enter it into the PF parameter.

Hardware usage

Pretty simple really. The two output relays can be used to control heaters. Either directly och replaced by solid state relays. The output is specified in percent and is controlled with slow PWM (that is they are pulsed on/off). 0-100% controls heater 1 (heat relay), 100-200% controls heater 2 (cool relay). So for example, if an output of 75% is specified, heater 1 will be on 75% of the time and heater 2 will be off. At 125% heater 1 will be on and heater 2 will be on 25% of the time. A negative percentage value is also allowed, which does the exact same thing, but with the elements reversed. This could be useful if during mashing for example, a lower power element is preferred over a higher powered one.

The output percentage is also used in thermostat mode, so if temperature is below setpoint, the output will be the specified one. If output is at or over the setpoint the output will be 0.

The unpopulated terminal on the STC can be used as pump control. The firmware will put this output in high impedance to turn pump on and pull it low to turn pump off. Pump output
Fig 1: Connection terminal of the LED dimmer

This can be used directly with an 8A LED dimmer for flow control of a 12V pump. 8A LED dimmer
Fig 2: LED dimmer

The schematic of the dimmer shows, that if you connect this output to the center pin of the potentiometer, you can switch between off and the manual setting. Note that you need to have a common ground for the STC and the dimmer. 8A LED dimmer schematic
Fig 3: LED dimmer schematic

Or, you could also use the output to control a mains powered pump using a solid state relay. SSR pump control
Fig 3: SSR pump control connection

Connect the positive input of the SSR to the pin on the STC and add a pullup resistor (220-470 ohm) to +5v (you can find that on the programming header on the STC). Connect the negative input on the SSR to ground (can also be found on the STC programming header).

Program algorithm

During the program, a single press on the power button will pause the program (during pause, a LED will flash and all outputs will be off). Press the power button again and the program will resume.

Graphical representation
Fig4: Graphical representation of the algorithm

Now, I will try as best I can, to explain the algorithm and key concepts in ‘english’.
The program starts off with a delay of Sd minutes (strike delay), during this time it will do nothing but wait. This can be useful if you want to delay the heating of strike water, so it will be warm by the time you need it (don’t recommend leaving it unattended, do so at your own risk). Sd can of course be set to 0 to start immediately.
Reaching strike temperature is done using SO output, and as you probably want to do this as fast as possible, you’d want to set SO to 100% (if you use one heating element) or 200% (for two elements), though you can use what will suit you and your system best.
Once strike temperature is reached, the alarm will go off if the corresponding APF flag is set and ‘St’ will flash on the display. It will also switch to thermostat mode with PO output. That means if/when temperature is below St, output will be PO. If it is at, or above St, output will be 0. If the alarm is not acknowleged within ASd (automatic shutdown delay) minutes, the program will be stopped. Once acknowledged (by pressing any button), the program will pauseif the corresponding APF flag is set (all outputs off) and during this pause you dough in your grains. Press the power button to continue the program.
In a similar way, for each of the mashing steps, SO will be used to reach the temperature fast, then switch to thermostat mode with PO output and hold the mash step temperature for the programmed duration.
When mashing is done, the alarm will go off again (again if the corresponding APF flag is set) and ‘bU’ (boil up) is flashing on the display. Thermostat action is still used. Acknowledge the alarm and the unit will pause (APF flag…) again. Remove the grains and optionally sparge manually. Press power button to resume.
SO output will be used to raise temperature quickly. Once Ht (hotbreak temperature) is reached, output is switched to HO (hotbreak output) for Hd (hotbreak duration) minutes. The purpose of this, is that as the wort reaches boiling temp, proteins clump together and a foam is formed on the surface. The added nucleation points as well as the insulating effect of the foam can easily contribute to boil over. The heat will shortly break down the proteins (hot break), that will settle to the bottom of the kettle. So, to avoid boil over the power is reduced during this period. As an educated guess, you might want to set Ht a degree or so shy of your normal boiling temperature. HO will probably be around 75% of bO and Ht should probably be around 15 minutes.
When Hd has passed, normal boil starts, with bO output. The timer also starts counting down the boil duration bd. When the timer matches a hop addition the alarm will sound and hdx will flash on the display. Acknowledge the alarm by pressing any button (and add the hops of course). Note that the hdx settings are in standard hop addition times as used in most recipies, that is the boil duration counted back from boil end.
Once the boil is completed, output is turned off and the alarm goes of (flashing ‘Ch’ for chill). Acknowledge and chill your wort.<p> An important note on ASd. This is in my opinion an important feature. Many of the steps in the program are timed. For example mash durations, boil duration and so on. But not every step is, for example, when ‘stepping up’ the temperature, the program will continue to heat until the temperature is reached, or during an alarm (except hop additions, during which the boil duration timer is running) when user input is required, during these times the timer is loaded with ASd instead and if not the condition is met within this timeframe, the program stops. This is of course for safety. ASd should therefore be set to the maximum of these duration + some wiggle room. For example, if it takes you around 35 minutes to reach strike temp and this is the longest of these delays, maybe set ASd to 45 minutes.
Also, a note on Pd. Power is controlled by pulsing on/off to the heating element. The lenght of an on/off cycle can be set with Pd. If you are using elements with high power draw (high in this context would probably be in the order of more than 1.5kW), exchanging the relays in the STC for an external solid state relay is probably a good idea. Using a solid state relay, a shorter period time is not a problem. Using the mechanical relays, you would probably want a longer period time, to limit wear from excessive switching. Though this can cause ‘pulsating’ boil and possibly wort scorching during mashing (depending on your setup of course).

Updates

Date Release Description
2015-XX-XX v1.00 First release